Battery Runtime Calculator

Estimate battery backup duration under load factoring in battery chemistry, discharge depth (DoD), and inverter loss.

Audited by UniqCalc Methodology Team • Formula Checked • Free & No Registration Required

Verified Mathematical Model & Formulation

Usable Energy (Wh) = Battery Voltage (V) × Capacity (Ah) × Depth of Discharge (%)
Runtime (Hours) = (Usable Wh × Inverter Efficiency) / Load (Watts)

Calculates total watt-hours of chemical storage, adjusts for safe depth-of-discharge (50% for Lead-Acid, 80-90% for Lithium LiFePO4), and factors in 85-90% DC-to-AC inverter conversion losses.

Configurable Parameters & Standard Units

  • Battery System Voltage (V): (Default: 12 v)
  • Battery Capacity (Ah): (Default: 100 ah)
  • Continuous Load (Watts): (Default: 150 w)
  • Depth of Discharge (50% Lead, 85% Lithium): (Default: 80 percent)
  • Inverter Efficiency (%): (Default: 90 percent)

Standard Worked Example & Practical Verification

Scenario: Running a 120W mini fridge on a 12V 100Ah LiFePO4 battery (85% DoD) via a 90% efficient inverter.

Calculated Solution
7.65 Hours of Continuous Backup Runtime

Practical Takeaway: Cycling a refrigerator with 33% compressor duty cycle will extend actual operational survival time to ~23 hours.

Frequently Asked Questions

Why shouldn’t Lead-Acid batteries be drained below 50%?

Deeply discharging standard lead-acid batteries below 50% state of charge accelerates irreversible plate sulfation and permanently shortens battery lifespan.